Fresh Air Handling Units (FAHUs) are widely used in commercial buildings, shopping malls, hotels, office buildings, hospitals, and other facilities that require controlled outdoor air ventilation.
When integrated into a Building Automation System (BAS) or Building Management System (BMS), a FAHU can be automatically monitored and controlled according to supply air temperature, operating schedules, indoor CO₂ concentration, fault conditions, and low-temperature protection requirements.
A typical FAHU automation system includes a DDC controller, supply air temperature sensor, return water temperature sensor, motorized water valve, fresh air damper, filter differential pressure switch, freeze protection thermostat, and fan status signals.
This guide explains the typical FAHU BAS monitoring points, control points, alarm functions, operating modes, water valve control logic, CO₂-based start/stop control, and freeze protection sequence.
- Typical FAHU BAS Architecture
- FAHU BAS Monitoring Points
- FAHU BAS Control Points
- Fault and Alarm Functions
- Historical Data Recording
- FAHU Operating Modes
- Supply Air Temperature Control Logic
- FAHU Shutdown Logic
- CO₂-Based Automatic Start/Stop Control
- Fresh Air Damper and Fan Interlock
- Freeze Protection Interlock
- Typical FAHU BAS I/O Point Summary
1. Typical FAHU BAS Architecture
A Fresh Air Handling Unit normally contains or interfaces with the following equipment and field devices:
- Supply air fan
- Fresh air / outdoor air damper
- Cooling coil
- Heating coil, where required
- Motorized chilled-water or hot-water valve
- Supply air temperature sensor
- Heating/cooling coil return water temperature sensor
- Filter differential pressure switch
- Freeze protection thermostat
- Programmable DDC controller
- BAS/BMS supervisory platform
The DDC controller receives digital and analog signals from field devices, executes the programmed HVAC control logic, and sends control commands to the fan, water valve, and fresh air damper.
Depending on the project, the controller can communicate with a supervisory BAS/BMS using protocols such as BACnet/IP, BACnet MS/TP, Modbus TCP, or Modbus RTU.
2. FAHU BAS Monitoring Points
The Building Automation System should continuously monitor the main operating conditions of each Fresh Air Handling Unit.
2.1 Digital Input Monitoring — DI
| Monitoring Point | I/O Type | Function |
|---|---|---|
| Fan Running Status | DI | Indicates whether the FAHU supply fan is running. |
| Fan Fault Alarm | DI | Indicates an abnormal fan operating condition or fault. |
| Manual / Auto Status | DI | Indicates whether the unit is operating in manual or automatic mode. |
| Filter Differential Pressure Alarm | DI | Indicates excessive pressure drop across the air filter and may indicate a dirty or blocked filter. |
| Fresh Air Damper Open/Closed Status | DI | Provides position status feedback from the fresh air or insulated outdoor air damper. |
| Freeze Protection Alarm | DI | Indicates activation of the low-temperature freeze protection switch. |
2.2 Analog Input Monitoring — AI
| Monitoring Point | I/O Type | Function |
|---|---|---|
| Supply Air Temperature | AI | Used for supply air temperature monitoring and water valve control. |
| Coil Return Water Temperature | AI | Used for hydronic monitoring and low-temperature freeze protection. |
| Motorized Water Valve Position Feedback | AI | Indicates the actual opening position of the motorized control valve. |
| Indoor CO₂ Concentration | AI | May be used for demand-based start/stop control in indoor pedestrian streets and similar public areas. |
3. FAHU BAS Control Points
3.1 Digital Outputs — DO
| Control Point | I/O Type | Function |
|---|---|---|
| FAHU Start / Stop Command | DO | Starts or stops the Fresh Air Handling Unit fan. |
| Fresh Air Damper Open / Close Command | DO | Opens or closes the outdoor air damper. |
3.2 Analog Outputs — AO
| Control Point | I/O Type | Function |
|---|---|---|
| Motorized Water Valve Command | AO | Modulates chilled-water or hot-water flow through the cooling/heating coil. |
4. FAHU Fault and Alarm Functions
4.1 Fan Fault Alarm
The BAS should continuously monitor the operating status of each FAHU fan.
When the unit receives a start command but the expected fan running status is not confirmed, or when a fan fault signal is detected, the BAS should generate a FAHU Fan Fault Alarm.
This allows facility operators and maintenance personnel to quickly identify abnormal equipment operation.
4.2 Freeze Protection Alarm
For FAHUs equipped with heating coils, freeze protection is particularly important because outdoor air is directly introduced into the unit.
- Heating coil surface / air temperature falls below 4°C; or
- Heating coil return water temperature falls below 10°C.
When either condition occurs, the BAS should generate a freeze protection alarm and immediately execute the required safety interlock sequence.
5. Historical Data Recording
The BAS should record important FAHU operating data for maintenance, fault analysis, performance evaluation, and energy management.
Typical historical trend data includes:
- FAHU operating status
- Supply air temperature
- Coil return water temperature
- Supply air temperature setpoint
Trend recording interval: 15 minutes
Historical data retention: not less than 5 years, where required by the project specification.
The BAS should also record fault alarm information, including:
- Alarm description
- Alarm type
- Time of occurrence
6. FAHU Operating Mode Selection
The FAHU supervisory interface should allow centralized management of all Fresh Air Handling Units.
Typical centralized functions include:
- One-click start of multiple FAHUs
- One-click stop of multiple FAHUs
- Unified supply air temperature setpoint adjustment
- Centralized operating mode switching
The system may provide three main operating modes:
- Subsystem Manual Mode
- Subsystem Schedule Mode
- Cloud / Supervisory Control Mode
6.1 Subsystem Manual Mode
When the system operates in Subsystem Manual Mode, subsystem scheduling and cloud supervisory control are disabled.
The user should be able to manually operate each FAHU from the subsystem control interface, including:
- Start or stop individual FAHU fans
- Adjust supply air temperature setpoints
- Adjust indoor pedestrian-street CO₂ concentration setpoints, where applicable
During system commissioning, authorized engineers should also be able to manually override the motorized water valve opening.
6.2 Subsystem Schedule Mode
When operating in Subsystem Schedule Mode, the BAS can automatically start and stop Fresh Air Handling Units according to configured time schedules.
Typical schedules may include:
- Pre-occupancy startup
- After-hours shutdown
- Weekday schedules
- Weekend schedules
- Holiday schedules
For FAHUs serving indoor pedestrian streets or similar public areas, operators may select either:
- Time Schedule Control, or
- CO₂-Based Automatic Start / Stop Control.
The BAS should transmit the relevant operating status points and logic selection points to the cloud or supervisory platform.
6.3 Cloud / Supervisory Control Mode
When the system operates in Cloud / Supervisory Control Mode, the FAHU can operate according to authorized commands issued by a higher-level supervisory or cloud platform.
Typical supervisory commands may include:
- FAHU start / stop
- Operating mode selection
- Supply air temperature setpoint adjustment
- CO₂ setpoint adjustment
The local DDC controller remains responsible for executing the actual HVAC control logic and safety interlocks.
7. FAHU Supply Air Temperature Control Logic
The FAHU automatically adjusts the motorized chilled-water or hot-water valve opening according to the difference between the measured supply air temperature and the configured supply air temperature setpoint.
In practical DDC applications, this function can be implemented using proportional or PID control.
7.1 Summer Cooling Operation
Supply Air Temperature > Setpoint + 1°C
Increase the chilled-water valve opening.
Supply Air Temperature < Setpoint − 1°C
Decrease the chilled-water valve opening.
When supply air temperature rises above the setpoint, the controller increases chilled-water flow through the cooling coil. When supply air temperature falls below the setpoint, the valve opening is reduced.
7.2 Winter Heating Operation
During winter operation, the control direction is reversed.
Supply Air Temperature > Setpoint + 1°C
Decrease the hot-water valve opening.
Supply Air Temperature < Setpoint − 1°C
Increase the hot-water valve opening.
7.3 Transitional-Season Operation
During suitable transitional-season ventilation conditions, mechanical heating or cooling may not be required.
The FAHU can continue supplying outdoor air while avoiding unnecessary chilled-water or hot-water consumption.
8. FAHU Shutdown Logic
When the Fresh Air Handling Unit stops, the system should first close the fresh air damper.
This prevents uncontrolled outdoor air from entering the building when the supply fan is not operating.
The water valve position should then be controlled according to the operating season:
| Operating Season | Water Valve Position When FAHU Stops |
|---|---|
| Cooling Season | Closed |
| Transitional Season | Closed |
| Heating Season | Approximately 50% Open |
9. CO₂-Based Automatic FAHU Start / Stop Control
For indoor pedestrian streets, shopping mall corridors, and other areas with variable occupancy, indoor CO₂ concentration can be used as an indicator of ventilation demand.
The BAS compares the measured indoor CO₂ concentration with the configured CO₂ setpoint.
9.1 High CO₂ Condition
If:
Measured CO₂ > Setpoint + 100 ppm
→ Start the corresponding FAHU.
This increases the amount of outdoor air supplied to the corresponding indoor area.
9.2 Low CO₂ Condition
If:
Measured CO₂ < Setpoint − 100 ppm
→ Stop the corresponding FAHU.
The ±100 ppm difference creates a control deadband and helps prevent frequent FAHU start/stop cycling around the CO₂ setpoint.
9.3 CO₂ Control Example
For example, if the indoor CO₂ setpoint is:
The control logic would be:
| Measured Indoor CO₂ | FAHU Operation |
|---|---|
| Above 900 ppm | Start FAHU |
| 700–900 ppm | Maintain current operating state |
| Below 700 ppm | Stop FAHU |
10. Fresh Air Damper and Fan Interlock
The FAHU fan and fresh air damper should operate with an interlock sequence.
A typical startup sequence is:
Where damper status feedback is provided, the controller can verify that the fresh air damper is open before allowing the fan to start.
When the FAHU stops:
This interlock helps prevent uncontrolled outdoor air infiltration when the FAHU is not operating.
11. FAHU Freeze Protection Interlock
Freeze protection should have a high priority in the FAHU control sequence.
Because a Fresh Air Handling Unit directly handles outdoor air, a heating coil may be exposed to very low air temperatures during cold weather.
- Heating coil surface / air temperature < 4°C; or
- Heating coil return water temperature < 10°C.
When a freeze protection condition is detected, the BAS should immediately execute the following sequence:
- Stop the FAHU fan.
- Close the fresh air damper.
- Generate a freeze protection alarm.
- Fully open the heating-water control valve.
This sequence prevents additional cold outdoor air from entering the FAHU and maximizes hot-water circulation through the heating coil.
12. Typical FAHU BAS I/O Point Summary
| BAS Point | I/O Type | Purpose |
|---|---|---|
| Fan Running Status | DI | Fan operating feedback |
| Fan Fault Alarm | DI | Fan fault monitoring |
| Manual / Auto Status | DI | Operating mode feedback |
| Filter Differential Pressure Alarm | DI | Dirty filter monitoring |
| Fresh Air Damper Open/Closed Status | DI | Damper position status |
| Freeze Protection Alarm | DI | Low-temperature protection |
| Supply Air Temperature | AI | Temperature monitoring and water valve control |
| Coil Return Water Temperature | AI | Hydronic monitoring and freeze protection |
| Motorized Water Valve Position Feedback | AI | Valve position monitoring |
| Indoor CO₂ Concentration | AI | Demand-based FAHU control where applicable |
| FAHU Start / Stop Command | DO | Fan enable / disable |
| Fresh Air Damper Command | DO | Fresh air damper open / close control |
| Motorized Water Valve Command | AO | Cooling/heating water valve modulation |
13. Why Proper FAHU BAS Control Logic Matters
A Fresh Air Handling Unit is responsible for introducing and conditioning outdoor air, so its control strategy is directly affected by outdoor temperature and climate conditions.
A properly designed FAHU Building Automation System can provide:
- Stable supply air temperature
- Reliable outdoor air ventilation
- Improved indoor air quality
- Automatic CO₂-based ventilation control
- Reduced unnecessary fan operation
- Improved HVAC energy efficiency
- Automatic filter alarm monitoring
- Fan fault detection
- Centralized BAS/BMS operation
- Historical operating data
- Automatic freeze protection
- Easier maintenance and troubleshooting
Freeze protection is particularly important for FAHUs operating in cold climates because the heating coil may be directly exposed to extremely cold outdoor air.
14. FAHU vs. AHU BAS Control
Fresh Air Handling Units and conventional Air Handling Units use many of the same BAS components, but their operating strategies are different.
| Control Function | AHU | FAHU |
|---|---|---|
| Primary Air Source | Usually mixed return air and outdoor air | Primarily outdoor fresh air |
| Return Air Damper | Commonly used | Usually not required |
| Fresh Air Damper | Often modulating | Typically interlocked with fan start/stop |
| Supply Air Temperature Control | Common | Common |
| Water Valve Modulation | Common | Common |
| CO₂ Control | Often adjusts outdoor air volume | Can be used to start/stop the FAHU |
| Freeze Protection | Important | Especially important |
Because a FAHU directly handles outdoor air, fresh air damper interlocking, supply air temperature control, and freeze protection are particularly important parts of its BAS sequence of operation.
Conclusion
A typical Fresh Air Handling Unit BAS control system monitors fan status, supply air temperature, return water temperature, filter differential pressure, motorized water valve position, fresh air damper status, indoor CO₂ concentration where applicable, and freeze protection signals.
The DDC controller can automatically control FAHU start/stop, fresh air damper operation, chilled-water or hot-water valve position, supply air temperature, scheduled operation, CO₂-based ventilation demand, and freeze protection interlocks.
By integrating these functions into a programmable DDC-based Building Automation System, a FAHU can provide reliable outdoor air ventilation while maintaining supply air temperature, improving indoor air quality, reducing unnecessary energy consumption, and protecting HVAC equipment under low-temperature conditions.
For BAS engineers, HVAC contractors, and system integrators, defining the correct FAHU monitoring points and sequence of operation is an important step in designing a reliable building automation system.
